AI-driven optimization

AI HVAC optimization that adjusts with approval and proves every saving

AI HVAC optimization uses live data and models to run heating, cooling and ventilation at the lowest energy that still meets comfort and air targets. Aqueduct baselines each site against weather, runs strategies such as demand-controlled ventilation, supply air temperature reset and load sequencing where control is enabled with owner approval, and verifies savings at the meter. Customers see 10 to 35% energy savings.

Powered by aQ EnergySmart, aQ AirSafe and Smart Controls, built on aQ Core
Rooftop cooling towers in a city
Site performance · this quarter
-8.4% vs expected
Weather normalizedBelow baseline
Demo data
Peak demand today
612 kW
Contracted 650 kWChillers sequenced
Demo data

Run every unit at the lowest energy that still meets comfort and air targets.

Fair baseline

Every saving measured against what the weather demanded

  • Degree-day regression

    Usage is regressed on cooling and heating degree days to give an expected value for every period and site.

  • Day-one baseline

    Uploading 6 to 12 months of utility bills sets the baseline before new metering is fully in place.

  • Savings in money

    Rate configuration from your own bills turns the gap between expected and actual use into cost.

Aqueduct digital twin with the live water balance equation
Site performance · this quarter
-8.4% vs expected
Weather normalizedBelow baseline
Demo data
HVAC engines

Ventilation and supply air matched to real conditions

  • Demand-controlled ventilation

    Outdoor air follows measured CO2 and occupancy, boosting when rooms fill and easing back when they empty.

  • Supply air reset

    Supply air temperature rises when zones are satisfied, trimming cooling and reheat without losing comfort.

  • Occupancy schedules

    Occupancy from sensors or defined schedules triggers automation rules for each site, floor or zone.

Large ducts in a plant space
Hall B · occupied
1,184 ppm CO₂
Ventilation adjusted
Demo data
Demand and plant

Loads sequenced and chillers run to the cooling load

  • Load sequencing

    Large loads are staggered so refrigeration, pumps and chillers do not all start in the same interval.

  • Plant efficiency

    Chiller efficiency in kW per ton comes from electrical input measured against cooling output.

  • Plant strategies

    Chilled water reset, pump pressure reset and chiller sequencing are recommended from measured data.

Aerial view of rooftop chillers
Peak demand today
612 kW
Contracted 650 kWChillers sequenced
Demo data
Old way vs the Aqueduct way

Building optimization, before and after Aqueduct

The old way
  • The plant is tuned once and drifts back within months.
  • Outdoor air runs at the design rate into empty rooms.
  • Chillers, pumps and loads start together and set the peak.
  • Savings are judged by comparing this year's bill to last year's.
  • Nobody can show which setpoint change saved what.
The Aqueduct way
  • Strategies run continuously and drift shows against baseline.
  • DCV sets outdoor air from measured CO2 and occupancy.
  • Load sequencing staggers starts against the demand profile.
  • Savings are measured against a weather-normalized baseline.
  • Command history ties every change to its measured result.
Problem

Why HVAC optimization rarely sticks

Most buildings have been tuned at least once. Few can show the saving a year later.

01

Savings nobody can prove

Without a weather-normalized baseline, a mild month looks like a win and a hot month looks like a failure.

02

One-off tuning

The plant is tuned once at commissioning. Schedules, setpoints and overrides drift back within months.

03

Fixed ventilation

Outdoor air is sized for a full building and delivered to empty rooms all day.

04

Everything starts at once

Chillers, pumps and process loads start together and set a demand peak the tariff charges for all month.

Strategies

Optimization strategies Aqueduct runs

Each strategy reads live data, acts where control is enabled with owner approval, and is measured against baseline.

StrategyWhat changesWhat it reads
Demand-controlled ventilation (DCV)Outdoor air follows measured CO2 instead of a fixed design rateZone CO2, occupancy, outdoor air damper position
Supply air temperature (SAT) resetThe supply air setpoint rises when zones are satisfied, spending less on cooling and reheatZone temperatures, supply air temperature, valve positions
Occupancy-driven schedulesUnits and fans run to real use, by sensor or by scheduleOccupancy sensors or defined schedules per site, floor or zone
Load sequencing and peak demandLarge loads are staggered and shifted out of peak tariff windowsFacility load in kW, tariff bands, demand profile
Chilled water supply temperature resetThe chilled water setpoint rises whenever the load allowsCooling load, valve positions, chiller power
Chiller sequencingThe right chillers run for the loadCooling load, kW per ton, runtime per chiller
Pump and fan pressure resetPumps and fans slow once valves and zones are satisfiedValve positions, loop differential pressure, duct static pressure
EconomizerMild outdoor air provides free coolingOutdoor air temperature, damper position, supply air temperature
How it works

Recommendations or automated control, your choice

Each site decides how far optimization goes. Many start with recommendations and enable control asset by asset.

01

Recommend

Aqueduct proposes setpoint and schedule changes with the evidence and the expected effect. Your team, BMS or plant manager carries them out.

02

Approve

Owners enable control per asset and per strategy. Nothing is written to equipment until that approval is in place.

03

Automate

Approved strategies run through Smart Controls over BACnet or Modbus via the field device network controller, or LoRaWAN relays for simple loads.

04

Protect

Lockouts block commands mid-action to prevent short cycling, and setpoint attainment and comfort compliance are tracked on every unit.

05

Verify

Savings are measured against the weather-normalized baseline, including any added pump or fan energy, and priced from your own rates.

Condenser fans seen from above
What we believe

Optimization only counts when the meter agrees with the model.

Talk to our team
One incident, start to finish

One optimization, start to finish

An illustrative rooftop unit serving an office floor.

Monitor

The RTU, zone temperature and CO2 sensors and the HVAC feeder report into aQ Core every 60 seconds.

Measure

HVAC energy runs above its weather-normalized baseline on weekday afternoons with the floor half occupied.

Identify

Outdoor air is held at the design rate while zone CO2 stays low. DCV and an occupancy schedule are recommended.

Act

With owner approval, DCV runs on the RTU through Smart Controls, with lockouts in place and every command logged.

Verify

HVAC energy settles below baseline, CO2 stays in range, and the priced saving becomes the new baseline.

Problem, solution, impact

Problem, solution, impact

What changes when optimization runs against a fair baseline.

The problemHow Aqueduct solves itThe impact
Energy

HVAC savings claimed but never measured.

Weather-normalized baselines, with every strategy verified against them.

Chiller kW per ton tracked against its own baseline, with each saving verified at the meter.

Air

Savings made by starving zones of fresh air.

DCV driven by measured CO2 and occupancy.

Ventilation that follows people, with CO2 kept in range.

Operations

Demand peaks set by loads starting together.

Load sequencing against the facility demand profile.

Peaks managed against the tariff, with every command logged.

Related

Signals the optimization engines read

All on one data layer, refreshed every 60 seconds.

Cooling degree daysHeating degree daysZone CO2OccupancySupply air temperatureChilled water delta TkW per tonPeak demandPower factorUtility rates
The strategies

Eight optimization strategies, opened up

Each strategy below has inputs it reads, logic it follows, guardrails it will not cross and a way its result is verified. Strategies run as recommendations by default. They act on equipment only where control is enabled, with owner approval, and every command is recorded in command history.

01 / 08

Run the right chillers for the load

Logic: compare the cooling load with each chiller's measured efficiency curve, and start or stop machines so the plant runs nearest its lowest plant kW per ton. A chiller is not added to cover low delta T alone.

  • Inputs: load in tons, kW per chiller, delta T, run status and runtime
  • Guardrails: minimum run and off times, chiller minimum flow, critical load redundancy kept
  • Verified by: plant kW per ton at matched load bands, before and after
Inputs
tons, kW per chiller, delta T
Guardrails
min run and off times, redundancy
Verified by
plant kW per ton by load band
02 / 08

Chilled water supply temperature reset

Logic: raise the chilled water setpoint in steps while every coil valve has margin; step it back down when the most open valve nears its limit, in the trim and respond pattern described in ASHRAE Guideline 36.

  • Inputs: coil valve positions, supply temperature, return humidity, pump kW
  • Guardrails: space humidity limit, maximum setpoint, pump energy counted
  • Verified by: chiller plus pump kW against the weather-normalized baseline
Inputs
valve positions, CHW temperature, humidity
Guardrails
dew point limit, pump kW
Verified by
chiller and pump kW
03 / 08

Condenser water temperature reset

Logic: set the condenser water target from wet bulb and load, aiming for the lowest combined chiller and tower fan kW rather than the coldest water possible.

  • Inputs: wet bulb, condenser water temperatures, chiller and tower fan kW
  • Guardrails: chiller minimum entering condenser temperature, tower fan limits
  • Verified by: combined chiller and tower kW against baseline
Inputs
wet bulb, CW temperatures, fan kW
Guardrails
chiller minimum condenser temperature
Verified by
combined plant kW
04 / 08

Supply air temperature reset

Logic: raise supply air temperature while zones are satisfied and reheat is in use; lower it when zones call for cooling. Warmer supply air cuts cooling and reheat, at some cost in fan energy.

  • Inputs: zone temperatures and cooling requests, supply air temperature, reheat valves
  • Guardrails: humidity limit, minimum and maximum supply temperature, fan kW counted
  • Verified by: AHU, chiller and reheat energy, with comfort compliance tracked
Inputs
zone demand, SAT, reheat
Guardrails
humidity, SAT limits, fan kW
Verified by
energy and comfort compliance
05 / 08

Duct static pressure reset

Logic: lower the static pressure setpoint until the most open VAV damper is close to fully open, then hold. The fan slows and its power falls steeply with speed.

  • Inputs: VAV damper positions, duct static pressure, fan speed and kW
  • Guardrails: minimum static, minimum airflow per box, rogue zones excluded
  • Verified by: fan kW at similar airflow and weather
Inputs
damper positions, static, fan kW
Guardrails
min static, rogue zones excluded
Verified by
fan kW
06 / 08

Demand-controlled ventilation

Logic: set outdoor air from measured zone CO2 and occupancy, boosting as rooms fill and easing back as they empty. In the product this runs as a CO2 ventilation optimization rule with saving, boosting and override targets.

  • Inputs: zone CO2, occupancy from sensors or schedules, outdoor air damper
  • Guardrails: area based minimum outdoor air kept, CO2 ceiling, override on demand
  • Verified by: HVAC energy against baseline with CO2 exposure in zone-hours alongside
Inputs
CO2, occupancy, OA damper
Guardrails
minimum outdoor air, CO2 ceiling
Verified by
energy and zone-hours of CO2
07 / 08

Optimal start and stop

Logic: start each unit as late as possible and still reach setpoint by occupancy, and stop it as early as the space allows, using how fast that space has recovered in similar weather.

  • Inputs: occupancy schedule, zone temperature, outdoor temperature, recovery history
  • Guardrails: setpoint reached by the occupied time, no stop while occupied
  • Verified by: runtime avoided and setpoint attainment at occupancy
Inputs
schedule, zone and outdoor temperature
Guardrails
setpoint at occupancy
Verified by
avoided runtime, attainment
08 / 08

Peak demand shaving

Logic: watch facility kW or kVA against the target, then stagger starts, pre-cool before the peak window and shed or delay non-critical loads in a set priority order.

  • Inputs: facility demand, tariff bands, load priorities, solar and storage
  • Guardrails: critical loads never shed, comfort limits, restart staggered
  • Verified by: peak interval demand against target, each action in command history
Inputs
kW or kVA, tariff, priorities
Guardrails
critical loads protected
Verified by
peak interval demand
Interactions

Where strategies trade energy against each other

Optimization in one place can cost energy in another. Each strategy is judged on the energy of everything it affects, not the one machine it changes.

StrategySavesCan costWhat Aqueduct counts
Chilled water resetChiller compressor energyPump energy in variable flow plants; dehumidificationChiller plus pump kW, space humidity
Condenser water resetChiller compressor energyTower fan energy and tower waterChiller plus tower fan kW, makeup water
Supply air temperature resetCooling and reheat energyFan energy at higher airflowAHU fan, chiller and reheat energy together
Static pressure resetFan energyComfort in starved zones if a box is faultyFan kW and comfort compliance per zone
Demand-controlled ventilationOutdoor air conditioning energyAir quality if sensors fail or driftEnergy with CO2 exposure in zone-hours
Optimal start and stopRuntime and fan energyA higher morning peak if every unit starts togetherRuntime avoided and peak interval demand
Peak shavingDemand chargesEnergy if pre-cooling is excessivePeak demand and kWh in the same period
How it works

From recommendation to an audited command

01

A finding with evidence

The strategy surfaces as a recommendation with the data behind it and the expected effect. Your team, BMS or plant manager can carry it out without Aqueduct writing anything.

02

Owner approval per asset and strategy

Where the owner chooses, control is enabled for one asset and one strategy at a time. Devices can be grouped into a control cluster, such as an RTU with its zone sensor, so they are operated and analysed as one system.

03

Rules with scope and thresholds

Automation rules are built with a scope of the device itself or site, floor or zone occupancy, a metric, a condition and a value, with a severity of info, warning or alert.

04

Protection while it runs

Lockouts block a new command while an existing one is still being acted on, which prevents short cycling. Setpoint attainment, comfort compliance and sequence exceptions are tracked live on every unit.

05

Command history closes the loop

Every command is recorded with whether it actually executed on the device. Savings are computed against the equipment's own baseline, so the result ties to a specific change.

Control quality

The signals that tell you a strategy is working

A strategy that saves energy but loses comfort, or fights another sequence, is not working. These are the measures Smart Controls keeps on every controlled unit.

Setpoint attainment

Where it goes wrong

Unit cannot reach what it is asked to do.

What we measure

Share of time at setpoint, banded good, watch or attention

What Aqueduct does

Strategy paused or reviewed when attainment falls into attention

Comfort compliance

Where it goes wrong

Savings made by letting zones drift.

What we measure

Share of occupied time within comfort limits per zone

What Aqueduct does

Reported next to every saving so neither is read alone

Sequence exceptions

Where it goes wrong

Two sequences fighting, or a unit out of order.

What we measure

Count of sequence exceptions per period

What Aqueduct does

Any exception raised for review

Short-cycle events

Where it goes wrong

Equipment starting and stopping too often.

What we measure

Short-cycle events per device

What Aqueduct does

Lockouts and rule review when events appear

Avoided runtime

Where it goes wrong

Equipment running when nothing needs it.

What we measure

Hours avoided through optimization this month

What Aqueduct does

Shown per device alongside energy saved

Communication health

Where it goes wrong

Commands sent to a device that is not listening.

What we measure

Device connection and data health

What Aqueduct does

Strategies depend on a healthy link; gaps are flagged

How it rolls out

A typical order for turning strategies on

Most sites move from read-only to control in stages, low risk strategies first, each one proved before the next.

1
Weeks 1 to 4

Read-only and baselines

Plant, AHUs, RTUs and meters connect read-only. Weather-normalized baselines are built from bills or history, and equipment baselines start.

2
Weeks 4 to 8

Schedules and optimal start

Occupancy schedules and optimal start and stop go first, because their effect is easy to see and easy to reverse.

3
Months 2 to 3

Air side resets and DCV

Static pressure reset, supply air temperature reset and demand-controlled ventilation, with comfort compliance and CO2 watched closely.

4
Months 3 to 6

Plant strategies

Chilled water reset, condenser water reset and chiller sequencing, where control is enabled, with owner approval, or through the existing plant manager.

5
Ongoing

Peak demand and review

Peak shaving against the tariff, with monthly review of savings, command history and any strategy that stopped paying back.

Questions

Common questions

AI HVAC optimization uses live data and models to run heating, cooling and ventilation at the lowest energy that still meets comfort and air targets. Aqueduct baselines each site against weather, runs strategies such as DCV and supply air temperature reset where control is enabled with owner approval, and verifies each saving at the meter.

Demand-controlled ventilation sets outdoor air from measured CO2 and occupancy instead of a fixed design rate, so less air is heated or cooled when rooms are lightly used. Aqueduct runs DCV where control is enabled with owner approval and tracks CO2 so savings do not cost air quality.

Supply air temperature reset raises the supply air setpoint when zones are already satisfied, cutting cooling and reheat energy. Aqueduct runs it as one of its HVAC engines, reading zone temperatures and valve positions, and tracks comfort compliance on every unit while it runs.

Aqueduct builds an expected baseline by regression on historical use plus cooling and heating degree days, then compares actual use against it. Uploading 6 to 12 months of utility bills gives a baseline on day one, and rate configuration turns the difference into money.

No. Aqueduct can run in recommendation mode, proposing setpoint and schedule changes that your team or existing BMS carries out. Where control is enabled with owner approval, Smart Controls apply approved strategies over BACnet, Modbus or LoRaWAN relays.

Yes. Aqueduct shows when a site draws the most, then sequences large loads so they do not start together and shifts pre-cooling and pumping out of peak tariff windows where control is enabled. Batteries, backup generation or solar can also be scheduled against the peak.

Yes. Aqueduct measures plant efficiency in kW per ton from electrical input and cooling output, finds low chilled water delta T, and recommends chilled water reset, pump pressure reset and chiller sequencing. These run through your plant manager or BMS, or through Smart Controls where control is enabled with owner approval.

Customers see 10 to 35% energy savings with Aqueduct, measured against a weather-normalized baseline rather than estimated. Results depend on the site, its equipment and how much control is enabled, which is why every saving is verified at the meter.

It is a reset logic in which a setpoint is trimmed a small step at a time while no equipment is asking for more, and pushed back when enough requests arrive. ASHRAE Guideline 36 describes it for resets such as static pressure and supply air temperature.

Sequence exceptions are counted on every controlled unit, and each strategy is judged on the combined energy of everything it affects. A strategy that raises another system's energy more than it saves shows up as no saving.

Device health shows connection rate and battery or capacitor voltage, so a failed or drifting sensor is visible. Rules depend on that data, so the team can pause a strategy rather than let it act on bad input.

Yes. Control is enabled per asset and per strategy, and can be switched back to recommendation only at any time. Command history shows every change that was made.

Usually occupancy schedules and optimal start and stop, because they are simple to verify and to undo. Air side resets and plant strategies follow once baselines and control quality are proved.

See Aqueduct on your own facility.

Bring a site, a utility bill or a question. We will show you where the loss is.