Healthy air

Hit air targets without burning energy.

A CO₂ spike in an empty building does not matter. One in a full meeting room does. Aqueduct overlays air quality with occupancy, tracks exposure in zone hours and raises fresh air when it is cheap to do so.

Powered by aQ AirSafe
Bright lounge with a garden view
Hall B · occupied
1,184 ppm CO₂
Ventilation adjusted
Demo data
Site air health · 24h
Unhealthy, driven by CO₂
Over 2000 ppm for 20+ minutes within an occupied hour. Increase ventilation, raise outdoor air supply or check the AHU economizer.
3 of 4 zones breaching · outdoor 67°F
Demo data

Hit air quality targets in occupied spaces without wasting energy on empty ones.

Air with occupancy

Every reading read against who was there

  • Per zone parameters

    CO2, VOC, temperature, humidity, carbon monoxide and particulates where sensors measure them.

  • Occupancy overlay

    Occupancy from sensors or schedules shows whether an event affected people or an empty room.

  • Portfolio ranking

    Sites are ranked by peak average CO2 and exposure, so attention goes where people are affected.

Top-down view of an open office floor
Hall B · occupied
1,184 ppm CO₂
Ventilation adjusted
Demo data
Findings and response

From a reading to a recommendation to a result

  • Standards referenced

    Each rating names the standard behind it, with a why this rating explainer.

  • Cheap fresh air

    When outdoor air is mild, the recommendation says so, because ventilation costs little right then.

  • Ventilation on approval

    Where control is enabled, AHUs, RTUs and relay fans respond under owner-approved rules.

Exposed ceiling with sprinkler pipes
Site air health · 24h
Unhealthy, driven by CO₂
Over 2000 ppm for 20+ minutes within an occupied hour. Increase ventilation, raise outdoor air supply or check the AHU economizer.
3 of 4 zones breaching · outdoor 67°F
Demo data
Exposure verified

Exposure duration tracked and every result recorded

  • Exposure in zone-hours

    Time above target is counted, because sustained exposure matters as much as the peak level.

  • Energy alongside

    Energy used for ventilation is measured with the air result, so neither is traded blindly.

  • Records for certification

    Continuous zone records support certification evidence. Aqueduct supplies the metrics, your team files.

Engineer in a hard hat working at a panel
CO₂ exposure · this week
Zones monitored24
Exposure38 zone hours
Worst zoneHall B
Demo data
Old way vs the Aqueduct way

Indoor air, before and after Aqueduct

The old way
  • A snapshot on a quiet day stands in for every day.
  • An alarm in an empty hall looks like one in a packed room.
  • Teams over-ventilate or wait for complaints.
  • Peaks are reported, but exposure time is never counted.
  • Air and energy are managed by different people and tools.
The Aqueduct way
  • Continuous readings show the real air during operations.
  • Occupancy overlay separates empty rooms from full ones.
  • Fresh air is raised when it is needed and cheap.
  • Exposure in zone-hours shows how long levels stayed high.
  • Air results and ventilation energy sit on one platform.
The problem

Air quality is a duration problem, not a snapshot.

The danger is a concentration sustained over time, in a space full of people.

01

Snapshot measurements

A one-off reading taken while production is stopped says nothing about the air during a full shift.

02

Alerts without context

Without occupancy, an alarm in an empty hall looks the same as one in a packed gate lounge.

03

Air against energy

More fresh air costs energy. Without outdoor conditions in view, teams either over-ventilate or wait for complaints.

How Aqueduct resolves it

From reading to recommendation to result.

Healthy air runs the same loop, with occupancy and weather in view.

01

Monitor

CO₂, VOC, temperature, humidity, carbon monoxide, pressure, light, motion and sound, per zone.

02

Measure

Exposure in zone hours, because duration matters as much as level. A health label for every site.

03

Identify

Patterns like nightly VOC spikes from cleaning products or CO₂ from vehicles idling near a loading dock, with the standard behind each finding.

04

Act

Increase ventilation, raise outdoor air or check the economizer. Demand controlled ventilation where control is enabled.

05

Verify

Exposure falls in the zones that breached, with the energy impact measured alongside.

Inside the air handler

Following the air through an AHU

Indoor air quality and ventilation energy are both decided inside the air handling unit. Each section of the unit has its own measurements and its own failure modes.

01 / 06

Outdoor air intake and damper

The outdoor air damper sets how much fresh air enters. Its minimum position should deliver the design ventilation rate; in practice dampers stick, linkages slip and minimums get changed and forgotten.

  • Damper command against actual position
  • Outdoor air temperature and humidity
  • Minimum position checked against measured outdoor air fraction
Measured
damper command and feedback, outdoor conditions
Risk
too little fresh air, or far too much
Aqueduct
compares damper position with the mixed air it produces
02 / 06

Mixing box and economizer

Return and outdoor air mix before the coils. When outdoor air is cool enough, the economizer opens the damper further for free cooling, up to a high limit set on temperature or enthalpy.

  • Mixed air temperature against return and outdoor
  • Economizer enable and high limit
  • Free cooling hours missed while the damper sat at minimum
Measured
return, outdoor and mixed air temperatures
Risk
free cooling lost, or humid air brought in
Aqueduct
flags economizer faults from the temperatures
03 / 06

Filtration

Filters protect people and coils. As they load, pressure drop rises, airflow falls or fan power rises to hold it. A better filter grade captures more fine particles but usually starts at a higher pressure drop.

  • Filter differential pressure trended
  • Fan kW and speed against pressure drop
  • Change triggered on condition, not the calendar
Measured
filter pressure drop, fan kW, PM2.5 in zones
Risk
wasted fan energy or bypassed filters
Aqueduct
maintenance alert on measured pressure drop
04 / 06

Cooling and heating coils

Coils condition the air and remove moisture. A fouled coil needs more valve opening for the same result; heating and cooling valves open together waste both.

  • Supply air temperature against valve position
  • Heating and cooling overlap with time and duration
  • Leaving air humidity where measured
Measured
valve positions, supply air temperature
Risk
simultaneous heating and cooling
Aqueduct
flags overlap and valve saturation
05 / 06

Supply fan and static pressure

Fan power rises steeply with speed, so a static pressure setpoint higher than the zones need costs energy every hour the unit runs.

  • Duct static against VAV damper positions
  • Fan speed and kW
  • Run hours against occupancy
Measured
static pressure, fan speed and kW
Risk
fan running fast and long for no reason
Aqueduct
static pressure reset where control is enabled
06 / 06

Zones and occupancy

The zone is where air quality is experienced. CO2, VOC, particulates, temperature and humidity are read per zone and overlaid with occupancy, so a reading is judged by whether people were there.

  • CO2 exposure counted in zone-hours
  • Occupancy from sensors or schedules
  • Plain language rating with the standard behind it
Measured
CO2, VOC, PM, temperature, humidity, occupancy
Risk
sustained exposure in occupied hours
Aqueduct
aQ AirSafe ratings and costed actions
The calculations

Ventilation numbers an engineer can check

Most ventilation questions come down to a few relationships. Aqueduct computes them from sensors the AHU usually already has.

QuantityHow it is calculatedSensors neededWhat it tells you
Outdoor air fraction, by temperature(mixed air minus return air) divided by (outdoor air minus return air)Outdoor, return and mixed air temperaturesThe share of supply air that is fresh; unreliable when outdoor and return are close
Outdoor air fraction, by CO2(return CO2 minus supply CO2) divided by (return CO2 minus outdoor CO2)CO2 in return, supply and outdoor airThe same share, from a second independent method
Outdoor airflowOutdoor air fraction times supply airflowSupply airflow, or fan speed with a known curveWhether the minimum delivers the design rate
CO2 above outdoorZone CO2 minus outdoor CO2Zone and outdoor CO2Ventilation per person, roughly, at steady occupancy
CO2 exposureHours above target, summed across zonesZone CO2 and timeDuration, not just peak, in zone-hours
Filter loadingPressure drop now against pressure drop when cleanFilter differential pressureWhen to change, and what loading costs the fan
Economizer opportunityHours when outdoor air was below the high limit while the damper sat at minimumOutdoor air temperature, damper positionFree cooling the unit failed to use
How it works

Setting up demand-controlled ventilation properly

01

Know the floor you cannot go below

Ventilation standards such as ASHRAE 62.1 combine a rate per person with a rate per floor area. The area part covers building materials and furnishings and does not fall with occupancy, so DCV never takes outdoor air below it.

02

Place and trust the sensors

CO2 sensors go in the breathing zone of the spaces that vary most, such as meeting rooms, classrooms and halls. Device health in aQ Core shows connection rate and power, so a dead or drifting sensor is found before it steers the unit.

03

Read CO2 with occupancy

CO2 tracks people, not every pollutant. Overlaying occupancy shows whether a rise came from a full room or something else, and VOC and particulate readings cover what CO2 does not.

04

Set the rule

The product's CO2 ventilation optimization rule sets saving, boosting and override targets for outdoor air. It runs on AHUs, RTUs or relay controlled fans where control is enabled, with owner approval.

05

Verify both sides

Ventilation energy is measured against the weather-normalized baseline, and CO2 exposure in zone-hours is reported next to it, so a saving made by starving rooms of air shows up immediately.

The energy and air trade-off

Where air quality and energy pull against each other

More fresh air almost always costs energy, but how much depends on the weather, the hour and the space. These are the points where the trade-off is decided.

Hot humid outdoor air

Where it goes wrong

Every extra unit of outdoor air must be cooled and dried, the most expensive air to bring in.

What we measure

Outdoor temperature and humidity, cooling coil load

What Aqueduct does

Outdoor air held to what occupancy requires in these hours

Mild outdoor air

Where it goes wrong

Fresh air is nearly free, yet units sit at minimum outdoor air.

What we measure

Outdoor air temperature against the economizer high limit

What Aqueduct does

AirSafe says so: when outdoor air is mild, more ventilation is low cost

Cold outdoor air

Where it goes wrong

Outdoor air must be heated, and oversized minimums run heating hard.

What we measure

Outdoor temperature, preheat and heating valve positions

What Aqueduct does

Minimum outdoor air matched to occupancy

Empty spaces

Where it goes wrong

Design ventilation delivered to rooms with nobody in them.

What we measure

Occupancy against outdoor air damper

What Aqueduct does

Occupancy rules reduce ventilation to the area based minimum

Crowded spaces

Where it goes wrong

CO2 climbs and stays high for long periods.

What we measure

Zone CO2, occupancy, exposure in zone-hours

What Aqueduct does

Boost ventilation, check the economizer, finding with the standard behind it

Filtration grade

Where it goes wrong

Higher grade filters raise fan energy; loaded filters raise it further.

What we measure

Filter pressure drop, fan kW, zone particulates

What Aqueduct does

Particulate results and fan energy shown together

Process and cleaning

Where it goes wrong

VOC or CO2 events from processes, cleaning crews or idling vehicles.

What we measure

VOC, CO2 and CO with time of day

What Aqueduct does

Pattern found, cause named, ventilation or exhaust fans triggered where enabled

How it rolls out

From first sensors to controlled ventilation

Air quality work starts with measurement, because most sites do not know their real air during operations.

1
Weeks 1 to 2

Sensors and AHU points

Zone air quality sensors are placed on the floor plan and AHU points are read over BACnet or Modbus. Zones are drawn around each sensor's coverage.

2
Weeks 2 to 6

The real picture

Continuous readings during real operation, overlaid with occupancy. Exposure in zone-hours shows which spaces matter.

3
Weeks 6 to 10

AHU diagnostics

Outdoor air fraction, economizer and filter findings route to maintenance with the data behind them.

4
Month 3 onward

Ventilation control

Demand-controlled ventilation and occupancy rules where control is enabled, with owner approval, verified on both energy and exposure.

Cooling towers by a river
What we believe

Healthy air and efficient buildings should never be a trade-off.

Talk to our team
Zone view

Every zone, overlaid with occupancy.

Air quality and occupancy on one timeline show when an event happens, in which zone, and whether anyone was there. Filter by site type, region and zone.

Zone view
CO₂ exposure · this week
Zones monitored24
Exposure38 zone hours
Worst zoneHall B
Demo data
Recommendations

A finding, the standard behind it and a costed action.

Each site gets a plain language rating with a "why this rating" explainer. When outdoor air is mild, Aqueduct says so, because more fresh air is cheap right then.

Recommendations
Site air health · 24h
Unhealthy, driven by CO₂
Over 2000 ppm for 20+ minutes within an occupied hour. Increase ventilation, raise outdoor air supply or check the AHU economizer.
3 of 4 zones breaching · outdoor 67°F
Demo data
Proof

Continuous, not a snapshot.

Air quality results depend on the site. We publish verified numbers as live sites report them.

Measured
24/7

per zone, overlaid with occupancy.

Tracked
Zone hours

so sustained exposure is caught, not just peaks.

Customer names withheld. Every result is anonymized.
Questions

Common questions

Where there is a pattern, like a cafeteria at lunch or a nightly cleaning crew, yes. Events like a truck parking at a dock cannot be predicted, and we say so.

Any air quality sensor that emits telemetry. We do not sell sensors as our core business, and installation runs through partners.

Per air quality event type, identified by zone and site, with thresholds you set.

From temperatures or CO2. Outdoor air fraction equals mixed minus return, divided by outdoor minus return, using either temperature or CO2. The temperature method is unreliable when outdoor and return temperatures are close, which is when CO2 helps.

Not when it is set up properly. The area based minimum is never cut, ventilation boosts as occupancy rises, and CO2 exposure is reported next to every energy saving.

CO2 is a good proxy for people driven ventilation, but not for every pollutant. VOC, particulates and carbon monoxide are measured separately where sensors are fitted.

On measured pressure drop, from the AHU or from a linked sensor in a control cluster. A maintenance alert fires when the threshold you set is crossed.

It depends on outdoor conditions. Bringing in fresh air on a mild day costs little, and on a hot humid day it costs a lot, which is why Aqueduct reads outdoor conditions before recommending more ventilation.

See Aqueduct on your own facility.

Bring a site, a utility bill or a question. We will show you where the loss is.