Energy efficiency

Cut waste and demand, verified at the meter.

You pay for peaks, for poor power factor and for equipment that runs when nobody is there. Aqueduct shows every source and feeder live, sequences the big loads and proves the saving against a weather normalized baseline.

Powered by aQ EnergySmart
Electrical cabinet with tagged breakers
Energy balance · active power
412Grid+146Solar=338HVAC+99Light+16Loss
Power factor 0.96Carbon today 1.9 t
Demo data
Peak demand today
612 kW
Contracted 650 kWChillers sequenced
Demo data

Cut waste and demand, and verify every saving at the meter.

Waste with a name

Whole-site energy split by source and load

  • Single line, live

    Sources, switchboard and feeders appear on the electric twin, color coded by loading and power factor.

  • Energy balance

    Grid, solar and backup equal HVAC, lighting, plugs, services and losses, so waste is attributed.

  • Gas included

    Gas is tracked in cubic meters and therms, so both volume and energy content are visible.

Circuit breakers in a distribution board
Energy balance · active power
412Grid+146Solar=338HVAC+99Light+16Loss
Power factor 0.96Carbon today 1.9 t
Demo data
Demand and control

Big loads sequenced, where control is enabled

  • Stagger and pre-cool

    Start-ups are staggered and spaces pre-cooled so the site stays under its demand target.

  • Occupancy driven schedules

    Schedules and automations follow occupancy from sensors or schedules, under owner-approved rules.

  • Auditable commands

    Lockouts prevent short cycling, and command history shows whether every command executed.

Condenser fans seen from above
Command history · RTU-2
Occupied mode07:00 · executed
Economizer on07:12 · executed
Lockout active07:13 · held
Demo data
Savings proven

Savings weather normalized, priced and verified at the meter

  • Adjusted baseline

    Regression on usage plus cooling and heating degree days sets the expectation before the claim.

  • Bills checked

    Supplier bills are checked against your meters, and usage changes are separated from rate changes.

  • Metrics for reports

    Verified results export as monthly metrics for the reports and certifications your team files.

Digital multimeter
Site performance · this quarter
-8.4% vs expected
Weather normalizedBelow baseline
Demo data
Old way vs the Aqueduct way

Energy, before and after Aqueduct

The old way
  • The bill says what the site used, never why.
  • Chillers, compressors and lighting all start at once.
  • Poor power factor adds cost that nobody sees.
  • Savings claims fall apart when the weather changes.
  • Supplier bills are paid without being checked.
The Aqueduct way
  • The single line shows every source, feeder and load live.
  • Big loads are sequenced under owner-approved rules.
  • The power triangle shows reactive waste on every node.
  • Weather normalized baselines make every saving defensible.
  • Every bill is checked against your own meters.
The problem

The bill tells you what happened. Not why.

Energy waste sits in demand peaks, power quality and savings that nobody can prove.

01

Peaks you pay for

When chillers, compressors and lighting all start together, the site jumps into a higher demand band.

02

Power you never use

When current and voltage are out of phase, apparent power rises. You use more infrastructure and pay for more than you get.

03

Savings nobody believes

Year over year comparisons ignore weather, so real savings and real waste look the same on paper.

How Aqueduct resolves it

Every feeder, every peak, every saving verified.

The same loop, applied to electricity and gas.

01

Monitor

The main meter and sub-meters per feeder, across grid, rooftop solar and diesel backup. Gas in cubic meters and therms.

02

Measure

A live energy balance: grid, solar and backup equal HVAC, lighting, plugs, services and losses. EUI and carbon every day.

03

Identify

Peaks, power factor, loading as a percent of rated kVA per feeder, system losses and meters that stopped reporting.

04

Act

Load sequencing, schedules and occupancy-based automations where Smart Controls are enabled. Tickets for everything else.

Nothing changes without owner approval.
05

Verify

Savings against a baseline built from history and cooling and heating degree days. Supplier bills checked against your meters.

How it works

Closing the energy balance, one level at a time

01

The equation every level must satisfy

At any node on the single line, power in equals the metered loads below it, plus whatever is unmetered, plus losses. On the aQ EnergySmart electrical twin the top line reads grid import plus solar plus backup generation equals HVAC, lighting, plugs, services and losses, in kW, with kVAR, kVA and power factor underneath. The same test is then repeated at every level beneath the incomer.

02

Incomer to main switchboard

The utility meter and the main LV switchboard meter should agree within the transformer loss. Aqueduct carries a transformer loss estimate and system losses on the twin, so a gap larger than that estimate points at the incomer metering, a CT ratio set wrong or an unmetered tap ahead of the switchboard.

03

Main switchboard to sub-main boards

The MSB outgoing feeders are summed against the MSB total. A remainder here usually means an outgoing feeder with no meter, often a later addition such as an EV charger, a kitchen extension or a tenant fit-out. Sub-metering coverage is printed on the twin, so the team sees what share of the load is actually explained.

04

Sub-main boards to distribution boards and loads

HVAC, lighting and plug feeders are closed against the boards that feed them, down to named equipment such as an RTU or a chiller. Each block shows loading as a percentage of rated kVA and its power factor, color coded, and NO DATA where a meter has stopped reporting, so a gap caused by a dead meter is never mistaken for waste.

05

Reading the unexplained remainder

A remainder that is flat around the clock is usually an unmetered constant load or a metering error. One that follows the working day is unmetered equipment in use. One that rises with outdoor temperature is unmetered cooling. One that appears overnight, when the site should be quiet, is the most valuable to chase, because it is energy nobody asked for.

Chiller plant

Chiller plant optimization, in the plant room's own terms

In hot climates cooling dominates the bill: up to 80 percent of a UAE building's electricity demand goes to cooling, according to Heriot-Watt University. These are the variables a chief engineer tunes, and what Aqueduct measures for each.

01 / 06

kW per ton, kW/kWr and COP from measured data

Plant efficiency is electrical input divided by cooling delivered. Cooling in tons is chilled water flow in gpm times delta T in degrees F, divided by 24; in metric terms, kWr is flow times specific heat times delta T. COP is the inverse of kW/kWr, or 3.517 divided by kW per ton.

  • Chiller kW from the feeder meter, cooling from BTU meter flow and header temperatures
  • Per chiller where feeders allow, and whole plant including pumps and tower fans
  • Trended against load and condenser conditions, never read as a single number
Measured
feeder kW, CHW flow, supply and return temperature
Derived
kW per ton or kW/kWr, COP, plant kW per ton
Aqueduct
tracks each chiller against its own baseline curve
02 / 06

Chilled water supply temperature reset

Every degree the chilled water setpoint can rise reduces compressor lift. The limit is the hardest working coil: once its valve is near fully open, the reset has gone far enough. Dehumidification is the other limit, because warmer chilled water removes less moisture.

  • Reset driven by coil valve positions, not by outdoor temperature alone
  • Space dew point or return humidity held as a hard limit
  • In variable flow plants, added pump energy is counted against the chiller saving
Measured
CHW supply temperature, valve positions, return humidity
Watch
pump kW rising faster than chiller kW falls
Aqueduct
recommends the reset, or applies it where control is enabled, with owner approval
03 / 06

Condenser water reset and cooling tower approach

Colder condenser water lowers lift and chiller kW, but costs tower fan energy. The right setpoint is where chiller plus tower fan kW is lowest, and it moves with wet bulb. Tower approach, leaving tower water temperature minus ambient wet bulb, shows whether the tower can deliver it.

  • Approach rising at similar load points to fouled fill, poor water distribution or a fan problem
  • Chiller minimum entering condenser temperature respected
  • Condenser approach on the chiller trended for tube fouling
Measured
CW supply and return, wet bulb where sensed, tower fan kW
Derived
tower approach, combined chiller and tower kW
Aqueduct
shows the combined optimum against what the plant is running
04 / 06

Staging and sequencing

Most chillers are most efficient somewhere in the middle of their range, not at full load. Staging decides when the next chiller starts and stops; sequencing decides which machine leads. Both should follow measured efficiency curves, not runtime rotation alone.

  • Measured kW per ton by load band for each chiller
  • Stage up only when load, not low delta T, demands it
  • Runtime balanced across machines within the efficiency rule
Measured
load in tons, kW per chiller, run status and runtime
Derived
efficiency curve per machine
Aqueduct
flags extra chillers running for the load
05 / 06

Delta T and low delta T syndrome

Chillers are selected for a design delta T. When return water comes back too cold, each chiller cannot load fully, so an extra chiller and its pumps start to carry the same load. The usual causes are coil valves that do not close, three way valves, fouled coils and AHU setpoints lower than the coils can reach.

  • Delta T trended against load, so the fault shows as a pattern
  • Decoupler flow direction watched in primary and secondary plants
  • The AHUs pulling the loop down identified by valve position and supply air temperature
Measured
supply and return temperatures, flows, valve positions
Risk
extra chillers and pumps for no extra cooling
Aqueduct
names the coils driving the low delta T
06 / 06

Primary and secondary versus variable primary flow

Primary and secondary plants run constant flow through the chillers and vary flow to the building, with a decoupler between them. Variable primary plants vary flow through the chillers themselves, which saves pump energy but has to protect each chiller's minimum flow with a bypass.

  • Primary and secondary: decoupler reverse flow is the sign of low delta T
  • Variable primary: bypass valve open time and chiller minimum flow
  • Loop differential pressure setpoint reset as valves allow
Measured
pump kW and speed, loop differential pressure, bypass flow
Derived
pump kW per ton of cooling
Aqueduct
shows pumping energy as part of plant efficiency
Air handling units

Where AHU energy hides

An AHU can hold every zone in comfort and still waste a large share of the energy it uses. These are the points a controls engineer checks, and what Aqueduct reads at each, over BACnet or Modbus through the field device network controller.

Supply air temperature

Where it goes wrong

A fixed low supply air setpoint overcools, then VAV reheat warms the air back up.

What we measure

Supply air temperature, zone temperatures, reheat valve positions

What Aqueduct does

Recommends supply air temperature reset from zone demand, with humidity as the limit

Duct static pressure

Where it goes wrong

A fixed static setpoint keeps the fan fast while most VAV dampers sit half closed.

What we measure

Duct static pressure, fan speed and kW, VAV damper positions

What Aqueduct does

Resets static pressure until the most open damper is nearly fully open

Economizer

Where it goes wrong

A stuck damper or a wrong high limit throws away free cooling, or brings in hot humid air.

What we measure

Outdoor, return and mixed air temperatures, damper command and position

What Aqueduct does

Checks damper command against feedback and mixed air against what the damper says

Outdoor air and CO2

Where it goes wrong

Outdoor air held at the design rate is heated or cooled for people who are not there.

What we measure

Zone CO2, occupancy, outdoor air damper position

What Aqueduct does

Demand-controlled ventilation on CO2, with the area based minimum kept

Schedules and occupancy

Where it goes wrong

Units run on a schedule set years ago, through holidays and empty floors.

What we measure

Run status against occupancy from sensors or defined schedules

What Aqueduct does

Occupancy-driven rules per site, floor or zone, where control is enabled

Simultaneous heating and cooling

Where it goes wrong

Heating and cooling valves open together, or reheat fights cold supply air.

What we measure

Heating and cooling valve positions, preheat and reheat status

What Aqueduct does

Flags overlap with time and duration as a standing finding

Coils

Where it goes wrong

A fouled or air bound coil needs a fully open valve to hold supply air, and drags down loop delta T.

What we measure

Valve position against supply air temperature, coil leaving water temperature

What Aqueduct does

Shows valve saturation at loads the coil should carry easily

Filters

Where it goes wrong

Rising pressure drop costs fan energy every hour; changes on a calendar waste filters or fan power.

What we measure

Filter differential pressure, fan kW and speed

What Aqueduct does

Maintenance alerts triggered on measured pressure drop, including from a linked sensor

RTUs and split systems

Rooftop units read component by component

The RTU twin in Smart Controls represents the unit's physical components and operating states, not a list of points. This is what each component reports and what goes wrong with it.

ComponentStates readWhat goes wrongWhat Aqueduct shows
Control panelMode: heat, cool, auto, fan; lockout warningUnit left in the wrong mode after serviceMode against schedule and occupancy
CompressorStatus, stage, cooling setpoint, supply air temperatureShort cycling, a stage failing to startShort-cycle events and setpoint attainment
Heating sectionHeating status, heating setpoint, supply air temperatureHeat and cool alternating in one dayMode changes and runtime share per component
Supply fanFan status, speed, fan overrunFan running 24 hours on an occupied scheduleFan runtime against occupancy
OA damper and mixingVent minimum, outdoor air temperature, damper percentageDamper stuck, economizer never enabledDamper command against position and mixed air
Zone and returnZone temperature, return air temperatureThermostat in a poor location or a narrow deadbandComfort compliance per zone
Short cyclingStarts per hour, on and off durationsOversized stage, narrow deadband, low airflow or charge problemsLockouts block new commands mid-action; events counted
Split systemsRun status from a relay or controller, room temperatureUnits left on in empty roomsOccupancy rules through LoRaWAN relays, where control is enabled
Peak demand and tariffs

What the tariff charges for, and the levers against each charge

An electricity bill is usually several charges stacked together. Each has a different physical cause, so each needs a different lever.

01 / 06

The single highest interval

Many commercial tariffs charge for the highest average demand in any one metering interval in the billing period, and some carry it into later months. One bad interval, often a morning start, can set the charge for the month.

  • Facility load in kW with the 24 hour demand curve on the twin
  • The interval that set the peak, and which feeders made it
  • Contracted or target demand drawn on the same chart
Measured
interval kW or kVA at the incomer
Lever
stagger starts, pre-cool, shed non-critical loads
Aqueduct
shows the coming peak and the loads behind it
02 / 06

Billing on apparent power

Where demand is billed in kVA, as is common under Indian tariffs with a contract demand, poor power factor raises the billed demand even when real power stays the same. Exceeding the contract demand can bring its own penalty.

  • kW, kVAR and kVA side by side at every node
  • Peak kVA against contract demand
  • The feeders whose reactive load lifts the peak
Measured
kVA, kW, kVAR at incomer and feeders
Lever
power factor correction and load sequencing
Aqueduct
shows kVA headroom against the contract
03 / 06

Reactive power and the power triangle

When current and voltage are out of phase, apparent power rises above real power. Cables, transformers and switchgear carry current that does no work, and the tariff may add a reactive penalty. The twin draws the power triangle for any node, with the phase angle.

  • Power factor per feeder, color coded on the single line
  • Reactive penalty shown in the twin footer
  • Capacitor bank stages checked against the power factor they should hold
Measured
PF, kVAR, kVA per node
Lever
correct at the feeders with the worst angle
Aqueduct
locates reactive load by feeder
04 / 06

Moving energy out of expensive hours

Under time of use rates, the same kWh costs more in peak windows. Pre-cooling before the window, running pumping and charging outside it, and sequencing refrigeration away from other big loads shifts cost without cutting service.

  • Usage split by tariff band from rate configuration
  • Schedules that move flexible loads out of peak bands
  • Every schedule change logged in command history
Measured
kWh by interval and tariff band
Lever
schedules, pre-cooling, staggered starts
Aqueduct
prices each band with your own rates
05 / 06

Grid, solar and backup generation

Many Indian sites run grid, rooftop solar and a diesel generator together. Knowing the hour by hour split lets the site run flexible loads when solar is producing and schedule backup generation or batteries against the peak.

  • Each source with active power and power factor on the twin
  • Solar output against facility load
  • Generator run hours and output recorded
Measured
grid import, solar generation, generator output
Lever
align flexible loads with solar, schedule storage
Aqueduct
one balance across all three sources
06 / 06

Feeder loading against rating

Each feeder shows its load as a percentage of rated kVA. A feeder running near its rating is a capacity risk; one running very lightly may hide oversized plant or poor power factor on a small load.

  • Percentage of rated kVA per feeder
  • Loading trended, not read once
  • Headroom known before new load is added
Measured
kVA per feeder against nameplate
Lever
rebalance loads before adding capacity
Aqueduct
green, amber or red on the single line
How it works

From degree days to money: how the baseline is built

01

Assemble the history

Six to twelve months of consumption, from meters already running or from uploaded utility bills. Six months is the minimum. Bills mean a new site gets performance results on day one instead of after a year of monitoring.

02

Pull the weather for the site

Historical weather for the site's location is fetched for the baseline period, and live weather after that. Cooling degree days are degrees above a reference temperature multiplied by the days that held; heating degree days are degrees below it.

03

Fit the regression

Consumption is regressed against cooling and heating degree days, in the form expected use equals a base load, plus a coefficient times CDD, plus a coefficient times HDD. The base term is what the site uses regardless of weather. The coefficients are how hard it works per degree day.

04

Compare actual with expected

Each period, the model gives expected use for the weather that actually happened. Below the adjusted baseline is saving; above it is waste. A hot month no longer looks like failure, and a mild one no longer looks like progress.

05

Price the difference

Rate configuration, taken from your own bills, turns the kWh or therm difference into money. Bill analysis separates a cost change caused by usage from one caused by a rate change, so a tariff increase is never mistaken for waste.

Measurement and verification

Proving a saving: the IPMVP options, and where each fits

The International Performance Measurement and Verification Protocol describes four ways to determine savings. The choice depends on the measure, the metering available and how much certainty the parties need.

OptionWhat is measuredWhere it fitsHow Aqueduct supports it
A: retrofit isolation, key parameterThe parameters that define the measure, others estimatedSimple, predictable measures such as a lighting retrofitFeeder or device data for the key parameter
B: retrofit isolation, all parametersAll energy use of the affected equipment, continuouslyA chiller, a VFD, an RTU under Smart ControlsEquipment baseline first, then savings against it
C: whole facilityThe utility or main meters for the whole siteSeveral measures with interacting effectsWeather-normalized site baseline from meters or bills
D: calibrated simulationA building model calibrated to measured dataNew construction or no usable baselineMeasured data to calibrate the model against
Routine adjustmentsWeather and other independent variablesEvery option, every periodCDD and HDD regression per site
Evidence trailWhat was changed, and whenAny savings claim under scrutinyCommand history shows each command and whether it executed
Breakers and wiring in a panel
What we believe

Energy savings only matter when the meter can prove them.

Talk to our team
Electrical digital twin

Your single line diagram, live.

Utility supply, solar, generators, the main switchboard and every feeder, color coded by power factor and loading. A power triangle and 24-hour demand for any node you select.

Electrical digital twin
Energy balance · active power
412Grid+146Solar=338HVAC+99Light+16Loss
Power factor 0.96Carbon today 1.9 t
Demo data
Demand

Stay under the contracted limit.

See when the site draws the most and sequence the big loads so they do not all start at once. Batteries, solar and backup generation can be scheduled against the curve.

Demand
Peak demand today
612 kW
Contracted 650 kWChillers sequenced
Demo data
Bill validation

Check every supplier bill against your own meters.

Compare what you are asked to pay with what your meters recorded, separate usage changes from rate changes, and use the same data to prove savings after a project.

Bill validation
Bill validation · September
Supplier billed184.2 MWh
Metered176.9 MWh
Difference7.3 MWh
Demo data
Proof

Verified at the meter, not estimated.

Energy results from live sites.

Energy
10 to 35%

energy savings customers see.

Real estate
20M+ sq ft

commercial real estate portfolio client.

Customer names withheld. Every result is anonymized.
Questions

Common questions

Yes. Keep your BMS and Aqueduct works across it, or replace building management and energy management on one platform.

Electricity by default, and gas in both cubic meters and therms.

Against an expected baseline built by regression on your historical use and cooling and heating degree days, then converted to money through your rate configuration.

Where Smart Controls are enabled, through LoRaWAN relays or Modbus and BACnet field devices, with an auditable command history.

It is load the meters below a node do not account for. Its shape tells you the likely cause: flat around the clock suggests an unmetered constant load or a metering error, a weather shaped remainder suggests unmetered cooling, and an overnight remainder is usually equipment nobody switched off.

It divides chiller electrical input from the feeder meter by cooling delivered, calculated from BTU meter flow and the chilled water supply and return temperatures. The figure is trended against load and condenser conditions, so a change in efficiency is not confused with a change in operating point.

Yes, where chilled water temperatures and flows are measured. Delta T is trended against load, and coil valve positions and supply air temperatures identify the air handlers pulling the loop down.

Yes. Real, reactive and apparent power are shown at every metered node, so peak kVA can be tracked against a contract demand, and the feeders whose reactive load lifts it can be found.

That depends on the measure and is agreed by the parties. Aqueduct supplies the measured data for whole facility baselines with weather adjustment, equipment level baselines for retrofit isolation, and a command history showing what was changed and when.

See Aqueduct on your own facility.

Bring a site, a utility bill or a question. We will show you where the loss is.