ASHRAE 62.1

ASHRAE 62.1 ventilation evidence, recorded zone by zone

ASHRAE 62.1 is the ASHRAE standard for ventilation and acceptable indoor air quality in buildings other than dwelling units. It sets minimum outdoor air rates and allows demand-controlled ventilation. Aqueduct records CO2, temperature, humidity and particulates per zone, tracks ventilation equipment states and verifies that demand-controlled ventilation holds air in range. Your engineer owns the design and compliance.

Powered by aQ AirSafe, built on aQ Core
Office reception with soft teal light
Hall B · occupied
1,184 ppm CO₂
Ventilation adjusted
Demo data
Site air health · 24h
Unhealthy, driven by CO₂
Over 2000 ppm for 20+ minutes within an occupied hour. Increase ventilation, raise outdoor air supply or check the AHU economizer.
3 of 4 zones breaching · outdoor 67°F
Demo data

Ventilation that meets the design intent every occupied hour, with the record to show it.

Air per zone

Every zone reports, so no room hides behind an average

  • Zone-level sensing

    CO2, VOC index, particulates, temperature and humidity are recorded in each zone a sensor covers.

  • Duration counted

    Exposure is tracked in zone-hours, because a level held for an hour matters more than a spike.

  • Occupancy overlaid

    Air readings sit next to occupancy, so only occupied-hour problems rise to the top.

Top-down view of an open office floor
Hall B · occupied
1,184 ppm CO₂
Ventilation adjusted
Demo data
Ventilation response

Demand-controlled ventilation you can see working

  • Equipment states

    Damper position, fan status and economizer state are read from connected AHUs and RTUs.

  • Plain recommendations

    Each finding names the zone, the guideline referenced and an action such as raising outdoor air.

  • Owner approved control

    Where control is enabled, ventilation targets change only with owner approval, and every command is logged.

Large ducts in a plant space
Site air health · 24h
Unhealthy, driven by CO₂
Over 2000 ppm for 20+ minutes within an occupied hour. Increase ventilation, raise outdoor air supply or check the AHU economizer.
3 of 4 zones breaching · outdoor 67°F
Demo data
Verified and recorded

Air back in range, energy cost counted, record kept

  • Verified in range

    After an action, the zone must return to its target band before the finding closes.

  • Energy counted

    The cost of extra outdoor air is shown, so air and energy are balanced rather than traded blindly.

  • Exportable history

    Per-zone records with min, max and average bands export for engineers and auditors.

Ceiling air unit under a glass roof
CO₂ exposure · this week
Zones monitored24
Exposure38 zone hours
Worst zoneHall B
Demo data
Old way vs the Aqueduct way

Ventilation evidence, before and after Aqueduct

The old way
  • Ventilation is proven once at commissioning, then assumed.
  • One return air sensor stands in for every room.
  • Outdoor air runs at full rate whether rooms are full or empty.
  • A stuck damper is found when occupants complain.
  • Air quality records are spot checks on a clipboard.
The Aqueduct way
  • Ventilation performance is recorded every occupied hour.
  • Each zone reports its own CO2, particulates and VOCs.
  • Outdoor air follows occupancy where control is enabled.
  • Damper and fan faults are flagged and routed to your CMMS.
  • Continuous zone records export whenever an engineer asks.

What ASHRAE 62.1 is and who it applies to

ASHRAE Standard 62.1, Ventilation and Acceptable Indoor Air Quality, covers spaces intended for human occupancy in commercial, institutional and other non-residential buildings. Residential dwelling units fall under a separate standard, ASHRAE 62.2. Many mechanical codes and green building programs, including LEED, reference 62.1 for minimum ventilation.

The standard gives procedures for designing ventilation, including the Ventilation Rate Procedure, which sets outdoor air by occupancy and floor area, and the Indoor Air Quality Procedure, which works from target contaminant levels. It also allows demand-controlled ventilation, where outdoor air is reset as occupancy changes, and includes operation and maintenance requirements for ventilation systems.

One point is often misread: 62.1 does not set an indoor CO2 limit. CO2 is used as a proxy for occupancy in demand-controlled ventilation. Aqueduct reports CO2 per zone for that reason, and references the specific guideline behind any rating it shows.

Evidence map

ASHRAE 62.1 requirement areas and the evidence Aqueduct supplies

Design compliance is the engineer's job. Aqueduct shows how the system runs once people are in the building.

Requirement areaEvidence Aqueduct supplies
Outdoor air deliveryOutdoor air damper position and economizer state from AHUs and RTUs over BACnet or Modbus, where connected
Demand-controlled ventilationCO2 and occupancy per zone with the ventilation response recorded, and air verified back in range
Occupancy assumptionsOccupancy from sensors or schedules, overlaid on zone air readings
Operation and maintenanceFault findings on dampers, fans and filters routed to your CMMS, with closures read back
Air quality in occupied spacesCO2, VOC index, PM2.5, PM10, temperature and humidity per zone, with exposure in zone-hours
RecordsPer-zone history with min, max and average bands, exportable for engineers and auditors
How it works

How Aqueduct supplies ventilation evidence

Awareness first, then action where control is enabled.

01

Sense every zone

Air quality sensors are placed per zone, the area a sensor speaks for, and report CO2, particulates, VOCs, temperature and humidity.

02

Overlay occupancy

A CO2 rise in an empty room is noise. Aqueduct aligns air readings with occupancy so the occupied hours stand out.

03

Explain the finding

The recommendation engine names the zone, the guideline behind the rating and a plain-language action such as raising outdoor air.

04

Act and verify

Where control is enabled, with owner approval, ventilation targets adjust. The zone is then verified back in range and the energy cost counted.

Exposed ceiling with sprinkler pipes
What we believe

Healthy air should be measured every hour people are breathing it.

Talk to our team

What stays with you and your engineer

Aqueduct records how air behaves. People own the design and the sign-off.

Ventilation design

Your mechanical engineer calculates outdoor air rates and selects the procedure. Aqueduct does not design ventilation.

Code and inspection

Compliance with the code your jurisdiction adopted is confirmed by the engineer of record and the authority.

Balancing and commissioning

Test and balance contractors and commissioning agents verify airflow. Aqueduct keeps the operational record afterward.

Standards and regulations

Related standards

Often used alongside 62.1.

ASHRAE 62.2ASHRAE 55 ASHRAE 170 ASHRAE 241 WELL AirLEED indoor environmental quality
Provisions that need data

The parts of ASHRAE 62.1 that live or die on measurement

ASHRAE 62.1 is mostly a design standard, but several of its provisions only hold up in operation if someone measures them.

01 / 05

Ventilation Rate Procedure outdoor air

The Ventilation Rate Procedure sets outdoor air from a people component and an area component per zone, then corrects for distribution effectiveness and system efficiency. In operation, the question is whether that outdoor air still arrives.

  • Outdoor air damper position and airflow at the air handler
  • Minimum outdoor air held during occupied hours
  • Drift after controls changes or damper failures
Data needed
outdoor airflow against the design minimum
Source
BMS airflow stations and damper points
Aqueduct
minimum outdoor air tracked per unit
02 / 05

Demand-controlled ventilation

Where demand-controlled ventilation resets outdoor air on CO2 or occupancy, the standard expects the reset to keep the breathing zone supplied. Poorly placed or uncalibrated sensors are the common failure.

  • CO2 per zone compared with the DCV sensor
  • Occupancy sensing for the people component
  • Alerts when CO2 rises while dampers sit at minimum
Data needed
zone CO2, occupancy and damper response
Source
AirSafe sensors and BMS points
Aqueduct
DCV checked against independent readings
03 / 05

IAQ Procedure

The IAQ Procedure lets a designer set outdoor air from contaminant targets rather than the rate table. It relies on knowing the contaminants and, in practice, on monitoring that the targets hold.

  • Particulates, VOCs and CO2 per zone
  • Targets entered per space type
  • Exceedances logged with duration
Data needed
contaminant concentrations over time
Source
multi-parameter air quality sensors
Aqueduct
targets tracked per zone
04 / 05

Dehumidification and moisture

The standard addresses humidity limits in occupied spaces under certain conditions and moisture control to limit mold growth. Humid climates and over-ventilated spaces both need watching.

  • Relative humidity per zone
  • Dew point alongside outdoor conditions
  • Time above your limit, per zone
Data needed
RH and temperature over time
Source
AirSafe sensors or BMS points
Aqueduct
humidity excursions by zone
05 / 05

Operations and maintenance

62.1 includes operations and maintenance requirements so ventilation keeps working after handover, including inspection of outdoor air dampers, filters and drain pans and keeping the system documentation current.

  • Filter loading from pressure points where available
  • Damper and fan faults routed to the CMMS
  • Records kept by unit and period
Data needed
equipment condition and maintenance history
Source
BMS, CMMS
Aqueduct
fault alerts and closure records
Provision to sensor map

ASHRAE 62.1 provisions mapped to meters and sensors

Use existing BMS points first. Add wireless sensors where a zone has no independent reading.

ProvisionWhat to measureMeters and sensorsAqueduct output
Ventilation Rate ProcedureOutdoor airflow per air handlerAirflow stations, damper position pointsOutdoor air against minimum, per unit
Zone ventilation effectivenessBreathing zone conditionsCO2 sensors at breathing heightZone CO2 trends and peaks
Demand-controlled ventilationOccupancy and CO2 per zoneCO2 and PIR occupancy sensorsDCV response checks
IAQ ProcedureDesign contaminantsPM2.5, PM10, VOC and CO2 sensorsConcentration against targets
Humidity limitsRelative humidity and temperatureTemperature and RH sensorsTime above limit per zone
Outdoor air qualityLocal outdoor conditionsOutdoor air quality or weather stationsOutdoor context for indoor readings
Operations and maintenanceFilter, damper and fan conditionFilter pressure points, fan statusMaintenance alerts and closures
How it rolls out

Getting ventilation evidence ready for review

A typical sequence for an office, school, hospital or campus that needs to show ventilation performance in operation.

1
Week 1

Collect the design basis

Gather design outdoor air minimums, zone schedules and any DCV sequences from the mechanical drawings and commissioning reports.

2
Weeks 2 to 4

Connect the BMS and place sensors

Read air handler and damper points over BACnet, and place CO2, temperature and humidity sensors in representative zones.

3
Weeks 4 to 8

Compare design with operation

Check outdoor air minimums, DCV response and humidity against design, and route faults to maintenance.

4
Month 3 onward

Keep the record

Monthly zone reports show CO2, humidity and outdoor air performance, with excursions and fixes recorded.

What we find

Where ventilation evidence usually breaks

Outdoor air dampers stuck at minimum or closed

A failed actuator or a linkage that slipped leaves the unit recirculating. Zone CO2 climbs while the BMS still reports a healthy setpoint.

DCV sensors that drifted

A single CO2 sensor in the return duct, never recalibrated, decides outdoor air for a whole floor. Independent zone sensors show the gap.

Schedules that miss real occupancy

Air handlers start after people arrive or stop before they leave. Occupancy data shows the mismatch hour by hour.

Sources1 references cited on this page
  1. ASHRAE Standards 62.1 and 62.2
Trusted at scale
Read the case studies
Deployed275+

sites in 21 countries run on Aqueduct.

Healthcare22 hospitals

and 9 clinics in one of India’s top hospital chains.

AirportsTop 25

US airport running water intelligence on Aqueduct.

Real estate20M+ sq ft

of commercial real estate under Aqueduct.

Manufacturing300 acres

FMCG manufacturing campus.

Food and dairyMajor dairy

operations run on Aqueduct.

Questions

Common questions

ASHRAE 62.1 is the standard for ventilation and acceptable indoor air quality in non-residential buildings. It sets minimum outdoor air rates and procedures for designing ventilation. Aqueduct records how ventilation performs in operation, zone by zone.

No. ASHRAE 62.1 does not set an indoor CO2 limit, and CO2 is used as an occupancy proxy for demand-controlled ventilation. Aqueduct reports CO2 per zone and names the guideline behind any rating it shows.

Demand-controlled ventilation resets outdoor air as occupancy changes instead of ventilating for full occupancy all day. Aqueduct records CO2 and occupancy per zone, adjusts ventilation targets where control is enabled with owner approval, and verifies the zone stays in range.

Design compliance is shown by your engineer's calculations and commissioning. Aqueduct adds the operational record: damper and economizer states from connected equipment and air readings per zone, so you can show the system keeps working after handover.

Aqueduct is device agnostic and reads air quality sensors that report CO2, VOCs, PM2.5, PM10, temperature, humidity and occupancy, mostly over LoRaWAN. Installation runs through partners.

No. Dwelling units are covered by ASHRAE 62.2. ASHRAE 62.1 covers commercial, institutional and other non-residential spaces, which is where Aqueduct is deployed.

It can, which is why Aqueduct counts the energy cost of each ventilation change. Demand-controlled ventilation ventilates for actual occupancy, so air targets are met without running outdoor air at full rate all day.

Place them in the breathing zone of representative occupied spaces, away from doors, supply diffusers and people's direct breath. Duct-mounted return sensors show the average, not the worst zone.

The Ventilation Rate Procedure sets outdoor air from tabulated rates per person and per area. The IAQ Procedure sets it from target contaminant concentrations, which makes monitoring central to proving it works.

Healthcare spaces are covered by ASHRAE 170, which sets ventilation for those spaces. Non-clinical areas in hospitals often fall under 62.1. See our ASHRAE 170 page.

Aqueduct can trend damper position, mixed air temperature and zone CO2, which together indicate whether outdoor air is arriving. Airflow stations give a direct measurement where they exist.

See Aqueduct on your own facility.

Bring a site, a utility bill or a question. We will show you where the loss is.